Checking code 1102: Serial transmission abnormality. Discharge temperature abnormality (Outdoor unit).
Meaning, detecting method
- When 140˚C or more discharge temperature is detected during operations (the first time), outdoor unit stops once, mode is changed to restart mode after 3 minutes, then the outdoor unit restarts.
- When 140˚C or more temp. is detected again (the second time) within 30 minutes after stop of outdoor unit, emergency stop is observed with code No. “1102” displayed.
- When 140˚C or more temp. is detected 30 or more minutes after stop of outdoor unit, the stop is regarded as the first time and the process shown in 1 is observed.
- 30 minutes after stop of outdoor unit is intermittent fault check period with LED displayed (1202).
Cause
- Gas leak, gas shortage.
- Overload operations.
- Poor operations of indoor LEV.
- Poor operations of OC controller LEV: Cooling : LEV1.